Tag - đại lý 1769-PA4

Allen Bradley 1769-PA4

Allen Bradley 1769-PA4

Thông số kỹ thuật:

1769-PA2 1769-PB2 1769-PA4 1769-PB4
Input Voltage, Nom. 120V AC or 240V AC 24V DC 120V AC or 240V AC 24V DC
Input Voltage Range 85…265V AC 19.2…31.2V DC 85…132V or 170…265V AC 19.2…31.2V DC
Real Input Power, Max. 44 W 50 W at 24V DC 90 W 100 W at 24V DC
Apparent Input Power, Max. 100 VA at 120V AC
130 VA at 240V AC
50 VA at 24V DC 200 VA at 120V AC
240 VA at 240V AC
100 VA at 24V DC
Typical Apparent Input Power at Full Load 80 VA 50 VA at 24V DC 160 VA 100 VA at 24V DCA
Line Loss Ridethrough 10 ms…10 s 5 ms…10 s
Frequency 47…63 Hz DC 47…63 Hz DC
Backplane Output Current, 0…55 °C, Max. 2 A at 5V DC
0.8 A at 24V DC
250 mA at 24V DC User
2 A at 5V DC
0.8 A at 24V DC
4 A at 5V DC
2 A at 24V DC
4 A at 5V DC
2 A at 24V DC
Backplane Output Current, 55…60 °C, Max. 2 A at 5V DC
675 mA at 24V DC
200 mA at 24V DC User
2 A at 5V DC
0.8 A at 24V DC
4 A at 5V DC
1.7 A at 24V DC
4 A at 5V DC
1.7 A at 24V DC
Fuse Front Access
Dimensions (HxWxD), Approx. 118 x 70 x 87 mm
(4.65 x 2.76 x 3.43 in.)
Height including mounting tabs is 138 mm (5.43 in)
Weight 0.5 kg (1.2 lb) 0.6 kg (1.4 lb)
Operating Temperature 0…60 °C (32…140 °F)
Nonoperating Temperature -40…85 °C (-40…185 °F)
Relative Humidity 5…95% noncondensing
Agency Certification
(when product is marked)
c-UL-us certified (under CSA C22.2 No. 142)
CE compliant for all applicable directives
Hazardous Environment Class Class I, Division 2, Hazardous Location, Groups A, B, C, D certified for U.S. and Canada